Circuit and load
Protection
Conductors
Choose the size
Automatic finds the smallest size that meets the code. A chosen size is checked, and the grounding conductor grows with it (250.122(B)).
Installation
Ground-fault check
Informational. A bolted line-to-ground fault at the load with an infinite source, through the circuit conductor and the EGC at 75 °C (Table 9). Set the multiple to the breaker’s instantaneous pickup or the current at which the fuse clears quickly.
Branch circuit
Circuit
Motor
Installation
Cross-section, to scale
Construction
Inputs
Basis
NEC 2023. Branch circuits by 210.19 and 210.20; feeders by 215.2 and 215.3; device ratings by 240.6(A); conductor protection by 240.4. Motors by Article 430 (430.6, 430.22, 430.32, 430.52, 430.62, 430.110); air-conditioning equipment by Article 440; fixed space heating by 424.4(B); storage water heaters by 422.11(E) and 422.13; EV charging by 625.41 and 625.42; dwelling feeders by 310.12.
Ampacity from Table 310.16 (Table 310.20 for messenger-supported conductors) with Tables 310.15(B)(1)(1), 310.15(B)(1)(2) and 310.15(C)(1), limited by the terminal temperature (110.14(C)) and the wiring method (334.80, 340.80, 338.10(B)(4)(a)). Equipment grounding conductors by 250.122. Raceway fill by Chapter 9 Tables 1, 4, 5, 5A and 8 and the published cable diameters (Note 9). Minimum cover by Table 300.5; overhead clearances by 225.18.
Voltage drop with Chapter 9 Table 9 at 75 °C and the stated power factor, at the load current. Cable constructions from the manufacturer specifications named with each drawing.