Finds the shortest cable that keeps every fault at the end within the rating.
Load
for voltage dropAvailable fault current
Fault current
Symmetrical rms, bolted faults
Voltage drop
Fault current along the cable
Inputs
Impedances and asymmetry ohms at the secondary voltage
Basis
Bolted, symmetrical rms faults by the ohmic method with complex impedances; prefault voltage at nominal; no motor or inverter contribution.
Source impedance from the three-phase and phase-to-ground fault currents and X/R. Transformer impedance from %Z and X/R; single-phase 120 V faults use 1.5R + j1.2X of the full winding (half-winding approximation).
Cable R and X from NEC Chapter 9 Table 9 (conduit); for direct buried and overhead cable, R from Table 9 and X from the geometry of the cable drawn. R corrected for temperature; phase-to-ground and phase-to-neutral faults return on the neutral.
Voltage drop by the IEEE Std 141 formula; transformer regulation at nameplate impedance with the primary at nominal voltage.