Transformer
Protection
Table 450.3(B)Conductors
Choose the sizes
Automatic finds the smallest size that meets the code. A chosen size is checked, and the grounding conductor grows with it (250.122(B)).
Installation
Transformer circuit
Primary
Secondary
Grounding and bonding
Raceways, to scale
Conductors from NEC Chapter 9 Tables 5 and 8
Transformer
Inputs
Basis
NEC 2023. Transformer protection by Table 450.3(B); device ratings by 240.6(A). Primary conductors protected by 240.4 and 240.4(B); secondary conductors by 240.21(C), without the next-size-up rule.
Ampacity from Table 310.16 with Table 310.15(B)(1)(1) and Table 310.15(C)(1), limited by the terminal temperature (110.14(C)). Grounding and bonding by 250.30, 250.122, Table 250.102(C)(1) and Table 250.66. Raceway fill by Chapter 9 Tables 1, 4, 5 and 8.
Voltage drop with Chapter 9 Table 9 at 75 °C and the stated power factor, at the rated current. Fault current at the secondary terminals with an infinite primary source.